FTP
Heating cable with a constant output and thermoplastic insulation (PVC) for anti-freeze protection and maintaining of lower temperatures (max. cable surface temperature is 90°C).
10, 15 and 20 W/m output line, version FTP, FTP/T, FTP/I, FTP/TP
FTSH
Heating cable with a constant ouptut and silicone insulation for maintaining of operational temperatures up to 150°C (max. cable surface temperature is 200°C). The contact points are fused.
20, 30 and 40 W/m output line, version FTSH, FTSH/T, FTSH/I, FTSH/TF
FTTH
Heating cable with a constant ouptut and fluorinepolymer insulation (Teflon) for maintaining of operational temperatures up to 150°C. Suitable for installations in chemical industry, where it can be exposed to the effects of agressive substances. The contact points are fused.
20, 30 and 40 W/m output line, version FTTH, FTTH/T, FTTH/I, FTTH/TF
FTP | FTSH | FTTH | |
Output | 10, 15 a 20 W/m | 20, 30 a 40 W/m | 20, 30 a 40 W/m |
Supplies | 2 mm2 | ||
Heating element | Ni-Cr resistance wire | ||
Supply insulation | silicone rubber | ||
Cable insulation | 105°C PVC | silicone rubber | fluorinepolymer |
Min and max. permitted surface temperature | -30°C to 90°C | -70°C to 200°C |
Output | Distance between joints | Max. cable length | Max. operational temperature [°C] | ||
[W/m] | [m] | [m] | FTP | FTSH | FTTH |
10 | 1.0 | 170 | 60 | - | |
15 | 0.8 | 150 | 50 | - | |
20 | 0.7 | 140 | 40 | 150 | |
30 | 0.7 | 120 | - | 140 | |
40 | 0.6 | 100 | - | 120 |
Application
Pipeline heating
References
CHP Plant at Michelin
Documents for download
FTP catalogue sheet
FTSH catalogue sheet
FTTH catalogue sheet
CE agreement declaration FTP
CE agreement declaration FTSH
CE agreement declaration FTTH
Accessories
FT/KIT/1, 2 - connecting and terminating kit for heating cables with a constant output in normal environments
You will find more accessories for the installation of heating cables in the FLEXKIT section.